Price and availability on request. Send us the quantity and delivery location in Oman.
Concentrate Heat Transfer Antifreeze Liq supplier and manufacturer in Oman
In short: Concentrate Heat Transfer Antifreeze Liq is our own RXSOL propylene glycol antifreeze, blended with corrosion inhibitor. You dilute it with water and use it in closed loop heating, air conditioning and low temperature refrigeration systems. We manufacture it, keep it in stock at our Barka warehouse, and we are the largest supplier of Concentrate Heat Transfer Antifreeze Liq in Oman. It is used in chillers, chilled water loops, cold rooms, process cooling and central heating installations. We deliver to Muscat, Sohar, Salalah and Duqm in 25 L cans, 210 L drums and 1000 L IBCs. Send us your quantity on WhatsApp for today's price.
When does a closed loop need glycol antifreeze?
In Oman the risk is rarely the weather. The risk is a chiller running a cold set point. Mixing propylene glycol into the water pays off in a recirculating chiller whenever the coolant set point is below 10 °C (48 °F). You need this fluid when:
- A new closed loop must be protected at its lowest operating or standby temperature.
- A test shows the glycol strength or freeze point in the loop is below what the system needs.
- Fluid testing shows the corrosion inhibitor is used up, the pH has drifted or the fluid is contaminated.
- A leak or repeated water top-ups have thinned the circulating fluid.
Freeze protection or burst protection: what your system needs
These are two different things, and the right mix depends on which one you need. Freeze protection keeps the fluid liquid and pumpable. Burst protection only stops pipes splitting. The fluid can still turn to slush.
| Your situation | Protection needed | What our fluid gives |
|---|---|---|
| Chiller or brine loop that must keep circulating at low temperature | Freeze protection | Fluid freeze protection to below -60 °F |
| Loop that stands idle and only needs to survive a shutdown | Burst protection | System burst protection to below -100 °F |
| Heating and hot side duty in the same loop | Heat transfer and stability | Operating range of -50 °F to 325 °F |
These figures are the limits of the fluid. The dilution for your loop depends on your lowest temperature, so we size it with you from the product data.
Concentrate Heat Transfer Antifreeze Liq for chillers, cold rooms and HVAC in Oman
The fluid is made for water-based HVAC systems. It keeps pipes free of corrosion without fouling them. The inhibitor package protects the metal while the glycol carries the heat and stops freezing. The fluid is also sold under our brand name FrioGel Neo.
It has a propylene glycol base, so it suits sites where low acute oral toxicity matters, or where incidental contact with drinking water is possible. Typical jobs in Muscat, Sohar, Salalah and Duqm are process chillers, air-cooled chiller loops, cold stores, food plants and central heating circuits.
Step by step: charging a closed loop
- Work out the system volume and the lowest fluid temperature. Decide whether you need freeze protection or burst protection.
- Choose the dilution from our dilution chart and technical data sheet, within the equipment maker's limits.
- If the loop is dirty or holds an unknown fluid, clean and flush it before you fill.
- Dilute the concentrate with clean, good quality water. Premix it in a tank where you can.
- Charge the loop, vent the air and circulate the fluid.
- Check the strength with a refractometer made for propylene glycol, and record the reading.
- Test the glycol strength, pH and inhibitor condition at regular intervals after that.
Mistakes to avoid
- Mixing up freeze and burst protection. A burst protected mix can still freeze in the chiller barrel and stop the pump.
- Using a generic glycol chart. Dilution charts differ from one formulation to another. Use the chart for this fluid.
- Too much glycol. An over-strong mix is thicker. It loads the pump and lowers heat transfer.
- Too little glycol. A weak mix also carries too little inhibitor to protect the loop.
- Topping up with plain water. Every top-up thins the mix. Retest after each one.
- Mixing fluids. Do not blend it with automotive antifreeze, ethylene glycol or another inhibited fluid without a compatibility check.
- Assuming food or drinking water approval. A propylene glycol base alone is not an approval for food or potable water contact.
Safety, storage and MSDS
Avoid contact with eyes and skin. Wear gloves and goggles when handling the concentrate, and wash after use. Contain any spill and keep it out of drains. Dispose of used fluid under local rules.
Store cans and drums closed, labelled and upright, in the shade. Read the MSDS before use: press "Get MSDS" at the top of this page to request it.
Concentrate Heat Transfer Antifreeze Liq or another product?
- Glycol antifreeze and corrosion protection in one fluid for a cold loop: Concentrate Heat Transfer Antifreeze Liq.
- Ready-to-use heat transfer fluid with no mixing on site: Heat Transfer Cool 50.
- Chilled water loop that needs no freeze protection, only treatment: Corrosion Inhibitor Multifunctional Closed Chilled Systems.
- Dirty loop before the first glycol fill: flush it with Commissioning Cleaner.
- Bacterial growth or slime in a closed loop: BIOCIDE for Closed Loop Chilled Water.
Concentrate Heat Transfer Antifreeze Liq price and quotation in Oman
The price of Concentrate Heat Transfer Antifreeze Liq depends on the pack, the quantity and the delivery point, so we quote every order. We stock it at Barka in 25 L cans, 210 L drums and 1000 L IBCs. Send us the quantity, the pack and the delivery location on WhatsApp +968 7733 3599 or through the quote form. Bulk and wholesale buyers, HVAC contractors and facility managers get volume prices. We deliver from Barka to Muscat, Sohar, Salalah and Duqm.
Overview
Concentrated Heat Transfer Antifreeze Liquid Blended with corrosion Inhibitor propylene glycol for Closed Loop low temperature refrigeration systems
Product description
Concentrated Antifreeze liquid Propylene glycol inhibited with the corrosion inhibitor resulting corrosion protection, as well as efficient heat transfer, in water-based, closed-loop heating and air-conditioning low temperature refrigeration systems systems.
Applications
Antifreeze for central heating installations and frozen water installations.
Dosage
This Inhibited Concentrate Heat Transfer Antifreeze Liq Propylene glycol heat transfer fluid has an operating temperature range of -50°F to 325°F; with fluid freeze protection to below -60°F, and system burst protection to below -100°F.
Also known as
FrioGel Neo
Notes
PROPYLENE GLYCOL based Concentrate Heat Transfer Antifreeze Liq supplier and exporter. Experts suggest in Airstack Chiller mixing of propylene glycol with water always be beneficial. Mixture in recirculating chillers is beneficial whenever the coolant temperature set point is below 10°C (48°F)
This fluid is specially formulated for HVAC systems to keep pipes free of corrosion without fouling.
This fluid is recommended for use in applications where low acute oral toxicity is important or where incidental contact with drinking water is possible.
Where we supply
Oman. Stocked at our warehouse in Barka, South Al Batinah, and supplied to Muscat, Ruwi, Mutrah, Seeb, Rusayl, Barka, Sohar, Shinas, Saham, Buraimi, Nizwa, Ibri, Sur, Salalah, Duqm, Khasab and every other governorate.
Ports and free zones. Port Sultan Qaboos (Mutrah), Mina Al Fahal, Sohar Port and Freezone, Port of Salalah and Salalah Free Zone, Port of Duqm and the Duqm Special Economic Zone, Port of Sur, Khasab Port and Al Mazunah Free Zone.
Industrial areas. Rusayl, Sohar, Barka (Sanaya), Raysut (Salalah), Nizwa, Sur, Buraimi and Duqm industrial estates, Knowledge Oasis Muscat, and oil and gas sites across Oman.
Beyond Oman. We have branches in the UAE (including Fujairah), India (Kandla, Kolkata, Visakhapatnam, Chennai and Mumbai), Kenya (Nairobi) and Canada, and we also supply to South Africa.
Questions about Concentrate Heat Transfer Antifreeze Liq
Who is the largest Concentrate Heat Transfer Antifreeze Liq supplier in Oman?
Oman Chem (Muscat & Barka for Business Trading) is the largest supplier of Concentrate Heat Transfer Antifreeze Liq in Oman. We manufacture this RXSOL propylene glycol fluid ourselves and keep it in stock at our Barka warehouse.
Is this fluid ethylene glycol or propylene glycol?
It is propylene glycol with a corrosion inhibitor blended in. This makes it a good choice where low oral toxicity matters.
Can I add it to the glycol already in my chiller?
Not without a compatibility check, because different inhibited fluids should not be mixed freely. If the existing fluid is unknown or contaminated, flush the loop and refill.
How do I check the glycol strength in my loop?
Use a refractometer made for propylene glycol. It shows straight away if the loop is over-diluted or too strong.
When should the fluid be replaced rather than topped up?
Replace it when testing shows the inhibitor is used up, the pH has drifted or the fluid is contaminated. A top-up only corrects the glycol strength.
What is the price of Concentrate Heat Transfer Antifreeze Liq in Oman?
We quote each order by pack, quantity and delivery point. Send your requirement on WhatsApp +968 7733 3599 or through the quote form for today's price.